Siemens MICROMASTER 440 User Manual

Page 31

Advertising
background image

Issue 10/06

6 Commissioning

MICROMASTER 440
Operating Instructions (Compact)

31

P1300 =...

Control mode

(enters the required control mode)
0 V/f with linear characteristic
1 V/f with FCC
2 V/f with parabolic characteristic
3 V/f with programmable characteristic
5 V/f for textile applications
6 V/f with FCC for textile applications
19 V/f control with independent voltage setpoint
20 Sensorless Vector control
21 Vector control with sensor
22 Sensorless Vector torque-control
23 Vector torque-control with sensor

Selection of torque setpoint *
(enters the source for the torque setpoint)

0 No main setpoint
2

Analog setpoint

4 USS on BOP link
5 USS on COM link (control terminals 29 and 30)
6 CB on COM link (CB = communications module)
7 Analog setpoint 2

Select motor data identification *

0 Disabled

Speed controller optimization *

0 Inhibited
In order to optimize the speed controller, the closed-loop vector control (P1300 =
20 or 21) must be activated. After the optimization has been selected
(P1960 = 1), Alarm A0542 is displayed.

End of quick commissioning
(start of the motor calculation)
0 No quick commissioning (no motor calculations)
1 Motor calculation and reset of all of the other parameters, which are not

included in the quick commissioning (attribute "QC" = no), to the factory
setting

2 Motor calculation and reset of the I/O settings to the factory setting
3 Only motor calculation. The other parameters are not reset.
NOTE
For P3900 = 1,2,3

→ P0340 is internally set to 1 and the appropriate data

calculated.

End of the quick commissioning/drive setting
If additional functions must be implemented at the drive inverter, please use the
Section "Commissioning the application" (refer to Section 6.4). We recommend
this procedure for drives with a high dynamic response.

0

P1500 =...

0

P3900 = 1

P1910 = ...

P1960 = ...

0

0

0

END

Advertising