Issue 10/06

6 Commissioning

MICROMASTER 440
Operating Instructions (Compact)

73

r0054 CO/BO: Control word 1

Displays the first control word (STW) of the frequency inverter and can be used to display
the active commands.

Bit00 ON/OFF1 0 NO 1 YES
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit02 OFF3: Fast stop 0 YES 1 NO
Bit03 Pulse enable 0 NO 1 YES

Bit04 RFG enable 0 NO 1 YES
Bit05 RFG start 0 NO 1 YES
Bit06 Setpoint enable 0 NO 1 YES
Bit07 Fault acknowledge 0 NO 1 YES

Bit08 JOG right 0 NO 1 YES
Bit09 JOG left 0 NO 1 YES
Bit10 Control from PLC 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES

Bit13 Motor potentiometer MOP up 0 NO 1 YES
Bit14 Motor potentiometer MOP down 0 NO 1 YES
Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES

r0063 CO: Actual frequency

Displays the actual frequency in Hz.

V/f

0

1,2

SLVC

(observer

model)

Encoder

P0400

P1300

160 ms

Frequency actual values:

Smoothed freq. actual value

Frequency actual value

Freq.act.value fr. the encoder

21,23

20,22

<20

0

P1300 = 21,23 and P0400 = 0 --> F0090

P0408

60

r0313

Smoothed speed act. value

r0313

60

r0022

r0021

r0063

r0061

r0067 CO: Act. output current limit

Displays valid maximum output current of inverter.

Motor

Inverter

Motor protection

P0640

r0067

P0305

Inverter protection

r0209

Min

r0072 CO: Act. output voltage

Displays output voltage.