2 Electrical Installation

Issue 10/06

MICROMASTER 440

8

Operating Instructions (Compact)

Input voltage range

3 AC 200 V – 240 V. ± 10 %

(Unfiltered)

Order No.

6SE6440- 2UC11

-2AA1

2UC12

-5AA1

2UC13

-7AA1

2UC15

-5AA1

2UC17

-5AA1

2UC21

-1BA1

2UC21

-5BA1

2UC22

-2BA1

2UC23

-0CA1

Frame Size

A B C

[kW]

0,12 0,25 0,37 0,55

0,75 1,1 1,5 2,2 3,0

Output Rating(CT)

[hp]

0,16 0,33 0,5 0,75 1,0 1,5 2,0 3,0 4,0

Output Power

[kVA]

0,4 0,7 1,0 1,3 1,7 2,4 3,2 4,6 6,0

CT-Input Current 1)

[A]

1,1 1,9 2,7 3,6 4,7 6,4 8,3 11,7 15,6

CT-Output Current

[A]

0,9 1,7 2,3 3,0 3,9 5,5 7,4 10,4 13,6

Fuse [A]

10 10 10 16 16 20 20 25 25

Recommended 3NA

3803 3803 3803 3805 3805 3807 3807 3810 3810

For UL specified

* * * * * * * * *

[mm

2

]

1,0 1,0 1,0 1,5 1,5 2,5 2,5 2,5 4,0

Input Cable, min.

[AWG]

18 18 18 16 16 14 14 14 12

[mm

2

]

2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0

Input Cable, max.

[AWG]

14 14 14 14 14 10 10 10 8

[mm

2

]

1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,5

Output Cable, min.

[AWG]

18 18 18 18 18 18 18 18 16

[mm

2

]

2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0

Output Cable, max.

[AWG]

14 14 14 14 14 10 10 10 8

[kg]

1,3 1,3 1,3 1,3 1,3 3,3 3,3 3,3 5,5

Weight

[lbs]

2,9 2,9 2,9 2,9 2,9 7,3 7,3 7,3 12,1

[Nm]

1,1 1,5 2,25

Tightening torques
for power terminals

[lbf.in]

(10) (13,3) (20)

Order No.

6SE6440- 2UC24-

0CA1

2UC25-

5CA1

2UC27-

5DA1

2UC31-

1DA1

2UC31-

5DA1

2UC31-

8EA1

2UC32-

2EA1

2UC33-

0FA1

2UC33-

7FA1

2UC34-

5FA1

Frame Size

C D E F

[kW]

4,0 5,5 7,5 11,0

15,0 18,5 22,0 30,0 37,0 45,0

Output Rating(CT)

[hp]

5,0 7,5 10,0 15,0 20,0 25,0 30,0 40,0 50,0 60,0

Output Power

[kVA]

7,7 9,6 12,3 18,4 23,7 29,8 35,1 45,6 57,0 67,5

CT-Input Current 1)

[A]

19,7 26,5 34,2 38,0 50,0 62,0 71,0 96,0 114,0 135,0

CT-Output Current

[A]

17,5 22,0 28,0 42,0 54,0 68,0 80,0 104,0

130,0 154,0

VT-Input Current 1)

[A]

28,3 34,2 38,0 50,0 62,0 71,0 96,0 114,0

135,0 164,0

VT-Output Current

[A]

22,0 28,0 42,0 54,0 68,0 80,0 104,0

130,0

154,0 -

Fuse

[A]

32 35 50 80 80 100 125

200

200 250

Recommended 3NA

3812 3814 3820 3824 3824 3830 3832 3140 3142 3144

For UL specified

3NE

* *

1817-0 1820-0 1820-0 1021-0 1022-0

1225-0

1225-0

1227-0

[mm

2

]

4,0 4,0 10,0 16,0 16,0 25,0 25,0 70,0 70,0 95,0

Input Cable, min.

[AWG]

12 12 8 6 6 3 3 2/0

2/0

3/0

[mm

2

]

10,0 10,0 35,0 35,0 35,0 35,0 35,0 150,0

150,0 150,0

Input Cable, max.

[AWG]

8 8 2 2 2 2 2

300

300

300

[mm

2

]

4,0 4,0 10,0 16,0 16,0 25,0 25,0 50,0 70,0 95,0

Output Cable, min.

[AWG]

12 12 8 6 6 3 3 1/0

2/0

3/0

[mm

2

]

10,0 10,0 35,0 35,0 35,0 35,0 35,0 150,0

150,0 150,0

Output Cable, max

[AWG]

8 8 2 2 2 2 2

300

300

300

[kg]

5,5 5,5 17,0 16,0 16,0 20,0 20,0 55,0 55,0 55,0

Weight

[lbs]

12,1 12,1 37,0 35,0 35,0 44,0 44,0 121,0

121,0 121,0

[Nm]

2,25 10

50

Tightening torques
for power terminals

[lbf.in]

(20) (89)

(445)

1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line

supply V

k

= 2 % referred to the rated drive converter power and a rated line supply voltage

of 240 V without line commutating reactor.

* UL listed fuses such as Class NON from Bussmann are required for use in America