6 Commissioning

Issue 10/06

MICROMASTER 440

34

Operating Instructions (Compact)

6.4

Commissioning the application

An application is commissioned to adapt/optimize the frequency inverter - motor
combination to the particular application. The frequency inverter offers numerous
functions - but not all of these are required for the particular application. These
functions can be skipped when commissioning the application. A large proportion
of the possible functions are described here; refer to the parameter list for
additional functions.

Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.


P0003 = 3

User access level *
1 Standard: Allows access into most frequently used parameters
2 Extended: Allows extended access e.g. to inverter I/O functions
3 Expert (For expert use only)

6.4.1

Serial Interface (USS)

P2010 =...

USS baud rate
Sets baud rate for USS communication.

P2011 =...

USS address
Sets unique address for inverter.

P2012 =...

USS PZD length
Defines the number of 16-bit words in PZD part of USS telegram.

P2013 =...

USS PKW length
Defines the number of 16-bit words in PKW part of USS telegram.

Possible
Settings:
4

2400 Baud

5

4800 Baud

6

9600 Baud

7 19200 Baud
8 38400 Baud
9 57600 Baud
10

76800 Baud

11

93750 Baud

12 115200 Baud

6.4.2

Selection of command source

P0700 =...

Selection of
command source
Selects digital command source.
0 Factory fault setting
1 BOP (keypad)
2 Terminal
4 USS on BOP link
5 USS on COM link
6 CB on COM link

P0700 = 2

Sequence control

Setpoint

channel

Motor

control

BOP

USS

BOP link

USS

COM link

Terminals

CB

COM link

START

1

6

0

2

127

2