6 Commissioning

Issue 10/06

MICROMASTER 440

38

Operating Instructions (Compact)

ADC1

ADC2
OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA

7

OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA

6.4.6

Analog input (ADC)



ADC type
Defines the analog input type and activates the monitoring
function of the analog input.

0 Unipolar voltage input (0 to +10 V)
1 Unipolar voltage input with monitoring

(0 to 10 V)

2 Unipolar current input (0 to 20 mA)
3 Unipolar current input with monitoring

(0 to 20 mA)

4 Bipolar voltage input (-10 to +10 V)
NOTE
For P0756 to P0760, the following applies:
Index 0 : Analog input 1 (ADC1), terminals 3, 4
Index 1 : Analog input 2 (ADC2), terminals 10, 11

P0757 =...

Value x1 of ADC scaling

P0758 =...

Value y1 of ADC scaling
This parameter represents the
value of x1 as a % of P2000
(reference frequency).

P0759 =...

Value x2 of ADC scaling

P0760 =...

Value y2 of ADC scaling
This parameter represents the
value of x2 as a % of P2000
(reference frequency).

Width of ADC deadband
Defines width of deadband on
analog input.

ASPmax

100 %

10 V
20 mA

V
mA

x

100%

%

P0760

P0758

P0759

P0761 > 0

0 < P0758 < P0760

||

0 > P0758 > P0760

ASPmin

P0757

P0761

P0757 = P0761

4000 h

Delay, ADC signal loss
Defines the delay time between the loss of the analog setpoint and fault message F0080
being displayed.

KL4

KL3

DIP switch

A

D

ADC

type

ADC

scaling

P

0757

P

0758

P

0759

P

0760

ADC

dead

zone

r0755

Pxxxx

r0752

P1000

ADC

ADC+

r0754

P0761

P0753

P0756

ADC

type

Setpoint

ADC channel

Wire

breakage

sensing

P0756

P0761

r0751

F0080

r0722
r0722.6

0

1

1.7 V

3.9 V

P0707

Pxxxx

Function

T

0

P0762

P0756 = ...

0

P0762 = ...

10 ms

0 V

0.0 %

10 V

100.0 %

0 V

P0761 =...