2 installing the samms-lv device, 2 grounding the device, 3 connecting the device to a control power source – Siemens MCC-3298 User Manual

Page 11: 5 communications connection, Figure 2.2 terminal block assignments

Advertising
background image

9

2 Installing the SAMMS-LV Device

2.4.2 Grounding the Device

As stated in Guideline 5, ground each motor controller at a
single ground point. The grounding path to earth must be
permanent and continuous. It must also be able to safely
conduct ground fault currents that may occur in the system to
ground through minimum impedance. The earth ground does
not carry any current under normal conditions.

Note: Do not ground the SAMMS auxiliary current sensor (ACT)
leads. (See figure 2.1.)

Connect a ground bus to the chassis of each controller or to the
chassis of the mounting equipment containing the earth ground
through a grounding conductor.

Refer to Article 250 of the National Electrical Code for informa-
tion about the types and sizes of wire conductors and methods
for safely grounding electrical equipment and components.

2.4.3 Connecting the Device to a Control
Power Source

The SAMMS-LV device requires a 12 VAC control power
source in order to operate. Connect the control power source
to terminals 5 and 6 located on the top of the relay.

2.4.4 Connecting Input and Output Devices
to the SAMMS-LV Device

Connect your devices to the input and output connections on
the SAMMS-LV device as illustrated in Figure 2.2.

2.4.5 Communications Connection

The SAMMS-LV device is equipped with an RS-485 commu-
nications port on the back of the device. The communications
port allows connection to a communications module which

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

SAMMS-LVX

LED

LED on

LED Flashing

Current
Unbalance

Impending
Trip

Overload
Trip

Incomplete
Sequence

External
Trip Alarm

CPU
Fault

Ground
Fault

> 40%

20 - 40%

> 110%

> 100%
< 110%

Overload

Start
Inhibit

Trip

Trip: Loss
of Load, or
Jam

Alarm: Loss
of Load or
Prcs Current

Trip: CPU
Failure or
Low Voltage

Trip

Alarm

CPU
Fault

Ground
Fault

Ready

Current
Unbalance

Impending
Trip

Overload
Trip

Incomplete
Sequence

External
Trip/Alarm

Reset/Test

ACT RETURN

ACT INPUT 1

ACT INPUT 2

ACT INPUT 3

ALARM RELAY OUTPUT

115VAC (CPT INPUT)

12VAC (CPT INPUT)

12VAC (CPT INPUT)

AC INPUT 4

AC INPUT 3

AC INPUT 2

AC INPUT 1

RETURN

OUTPUT 3

OUTPUT 2

OUTPUT 1

Figure 2.2 Terminal block assignments

Advertising