Appendix A Technical Specifications

Appendix A - Technical Specifications of the SAMMS-LV Device

Motor Control Specifications

Inputs

SAMMS-LVX:
Six pushbuttons
Four remote inputs

SAMMS-LVE:
Six pushbuttons
Two remote inputs

Outputs

SAMMS-LVX:
Three coil drivers
Three light bars
One programmable alarm contact

SAMMS-LVE:
One coil driver
Two light bars

Diagnostic LEDs

* Current unbalance
* Impending trip
* Overload trip
* External trip
* Incomplete sequence
* Ground fault
* CPU fault
* Ready
* Light bar flashes (timer timing)
* Impending trip LED flashes (motor temperature warning)
* Overload trip LED flashes (start inhibit)
* CPU LED ON (momentary loss of voltage)

Current Ranges:
0.3 - 1.5A
1.2 - 6A
4.8 - 24A
10 - 36A
10 - 45A
20 - 90A
40 - 135A
80 - 270A
160 - 540A

Overload Relay Size:
1A
1B
1C
2A
2B
3
4
5
6

Permissible CT Ratios

5A secondary CT ratios (functions
F4A & F5A)

Overload Relay Size

1A

1B
1C

2A

2B

3
4
5
6

Permissible CT Ratios
N/A
N/A
30:5, 40:5
30:5, 40:5, 50:5
30:5, 40:5, 50:5
30:5, 40:5, 50:5, 75:5, 100:5, 150:5
50:5, 75:5, 100:5, 150:5
100:5, 150:5, 200:5, 250:5, 300:5, 400:5
200:5, 250:5, 300:5, 400:5, 500:5, 600:5