3 operating the samms-lv device – Siemens MCC-3298 User Manual

Page 30

Advertising
background image

28

3 Operating the SAMMS-LV Device

Function

Number

Function Description

Range

Step Size

Default Value

F12

Select ground fault protection or

warning. ON means protection; OFF

means warning.

ON/OFF

N/A

OFF

F12A

Select ground fault pick-up current

value.

1A: 1.5A

1B: 2A-5A

1C: 2A-I

2A: 2A-I

2B: 2A-I

3: 2A-I

4: 2A-I

5: 5A-I

6: 10A-I

I is the value of I for

OLR#2 if F3 is not set to

OFF. If F3 is OFF, I is

the value of I for

OLR#1.

N/A

1A

1A

1A

1A

1A

1A

1A

1A

1.5A

5A

5A

10A

10A

10A

10A

10A

20A

F13

Set programmable timer #1.

OFF - 200 seconds

1 second

OFF

F14

Set programmable timer #2.

OFF - 200 seconds

1 second

OFF

F15

Display the average line current and the

individual line currents.

1A: 0.0 - 16.8A

1B: 0.0 - 67.1A

1C: 0.0 - 99.9A

100 - 268A

2A: 0.0 - 402A

2B: 0.0 - 503A

3: 0.0 - 1006A

4: 0.0 - 1509A

5: 0.0 - 3018A

6: 0.0 - 6036A

0.1A

0.1A

0.1A

1A

1A

1A

1A

1A

1A

2A

N/A

F16

Display the most recent trip current.

1A: 0.0 - 16.8A

1B: 0.0 - 67.1A

1C: 0.0 - 99.9A

100 - 268A

2A: 0.0 - 402A

2B: 0.0 - 503A

3: 0.0 - 1006A

4: 0.0 - 1509A

5: 0.0 - 3018A

6: 0.0 - 6036A

0.1A

0.1A

0.1A

1A

1A

1A

1A

1A

1A

2A

N/A

F17

Display the percentage current

unbalance. OFF is displayed if

unbalanced protection is off.

0 - 100%

1%

N/A

FLC

FLC

FLC

FLC

FLC

FLC

FLC

FLC

FLC

Table 3.8 Motor control and protection functions (page 2 of 3)