3 Operating the SAMMS-LV Device

b.When phase unbalance protection is disabled (OFF), the

Phase Unbalance LED remains off, unbalanced condi-

tions have no effect on protection, and F17 (Display

Unbalanced Current) displays OFF.

2. To change the setting, you must be in program mode.

3. To change the setting, press the UP or DOWN key to display

the setting options, then press ENTER to select the setting

that is shown. The display blanks while the ENTER key is

pressed.

4. Repeat Step 3 if you select an incorrect setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to go to other functions.

F10 - Display Time to Restart

1. Press the LIST key to view the time remaining before the

motor can be restarted. The time is displayed in seconds.

While the motor is cooling, the time to restart counts down

from the maximum winding temperature allowed to the

steady-state, full-load temperature. The display is always

zero if the motor is not in a start inhibit mode. If a time to

restart displays, the motor can only be restarted by an

emergency restart (see F11).

2. The UP, DOWN, and ENTER keys are disabled.

3. Press the (F)unction key to go to other functions.

F11 - Emergency Restarting

1. Press the LIST key to view the emergency restart setting (ON

or OFF). The factory default is OFF. With emergency restart

enabled (ON), you can restart the motor after the overload

relay is reset (manually or automatically), even when the time

to reset is not zero. When you initiate an emergency restart,

the motor conditions are reset to zero to simulate a com-

pletely cold start. The emergency restart function is auto-

matically disabled after any restart (emergency or normal),

and you must manually re-enable the emergency restart

function by setting F11 to ON.

2. Emergency restart can be enabled in either the program

mode or the display mode.

3. To change the setting, press the UP or DOWN key to display

the setting options, then press ENTER to select the setting

that is shown. If the selected setting is ON, skip to Step 5.

4. If the selected setting is OFF, the display blanks while the

ENTER key is pressed. When the ENTER key is released, the

setting is changed to OFF. Skip to Step 6.

5. If the selected setting is ON, “SUrE” is displayed when you

release the ENTER key. Press ENTER again to make the

change to ON.

Note: The motor can be damaged if restarted before it is

allowed to cool. The “SUrE” display allows you to reconsider

your actions before pressing the ENTER key a second time

to select the ON setting.

6. Repeat Step 3 if you select an incorrect setting.

7. If you are in the program mode, press and hold the (F)unction

key for several seconds to exit. The display will show “Prog.”

Press the UP or DOWN key to change to the display mode.

8. Press the (F)unction key to go to other functions.

F12 - Ground Fault Protection or Warning

1. Press the LIST key to view the active ground fault detection

setting (ON or OFF). The factory default setting is warning

(OFF), and the other setting is protection (ON).

a. When warning (OFF) is selected, the Ground Fault LED

flashes if the ground current increases beyond the pickup

level. The LED stops flashing as soon as the current drops

below the pickup level.

b.When protection (ON) is selected, a ground current above

the pickup level will cause a trip. The motor stops, and the

Ground Fault LED is steadily lit. You must reset the unit

before the motor can be restarted.

2. To change the setting, you must be in program mode.

3. To change the setting, press the UP or DOWN key to display

the setting options, then press ENTER to select the setting

that is shown. The display blanks while the ENTER key is

pressed.

4. Repeat Step 3 if you select an incorrect setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to go to other functions.

Advertising