Appendix a technical specifications – Siemens MCC-3298 User Manual

Page 47

Advertising
background image

45

Appendix A Technical Specifications

Dimensions

SAMMS-LV

6.25 inches W; 6.00 inches H; 2.125 inches D

Handheld Communicator

3.15 inches W; 5.7 inches H; 1.37 inches D

Environments

Operating temperature range

-25º C to +70º C.

Storage temperature

-40º C to +85º C.

Relative humidity

5 to 95% non-condensing.

Altitude

6600 ft.

Vibration

5 g's at a frequency range of 10 to 60 Hz.

Electrostatic discharge

No hardware failures at 15 kV at any point in the front of the unit.

Electromagnetic interference

5 kV repeated pulses, per UL-991 and ANSI C37.90A.

Radio frequency interference

Up to 95 MHz and 61.3 V/M field strength

Control Power Specifications

Unit powered by

12 VAC (+10%, -15%) supply

Power requirements

4VA

Control circuit inputs

120 VAC or 125 VDC (+10%, -15%)

Control circuit outputs

120 VAC (+10%, -15%)

Maximum output loading allowed
for continuous operation

1.0A for each output energized
Maximum leakage current allowed: 5mA

Frequency

50 Hz: +4%, -5%
60 Hz: ± 5%

Advertising