Advertising
background image

27

3 Operating the SAMMS-LV Device

Function

Number

Function Description

Range

Step Size

Default Value

F0

Select ambient temperature.

0 - 70º C

5º C

40º C

F1

Display (or change for SAMMS-LVE)

the control circuit number,

Enable/disable incomplete sequence

status.

0 - 9999

1

N/A

F2

Display the size for single-speed

controller, or the high-speed size for

two-speed motor controllers.

1A, 1B, 1C, 2A, 2B, 3,

4, 5, 6

As shown

N/A

F3

Display the low-speed size for

two-speed controller. F3 is OFF for

single-speed motor controllers.

1A, 1B, 1C, 2A, 2B, 3,

4, 5, 6, OFF

As shown

N/A

F4

Select the full-load current setting (I )

for the size for single-speed motor

controller or the high-speed size for

two-speed motor controllers.

1A: 0.3 - 1.5A

1B: 1.2 - 6A

1C: 4.8 - 24A

2A: 10 - 36A

2B: 10 - 45A

3: 20 - 90A

4: 40 - 135A

5: 80 - 270A

6: 160 - 540A

0.1A

0.1A

0.1A

1A

1A

1A

1A

1A

2A

0.3A

1.2A

4.8A

10A

10A

20A

40A

80A

160A

F4A

Display the primary current if 5A

secondary CT's are used.

Function of size in F2

Function of size in F2

OFF (denotes

SAMMS sensors

in use)

F5

Select the full-load current setting (I )

for the low-speed size for two-speed

motor controllers. F5 is OFF for single

speed motor controllers.

1A: 0.3 - 1.5A

1B: 1.2 - 6A

1C: 4.8 - 24A

2A: 10 - 36A

2B: 10 - 45A

3: 20 - 90A

4: 40 - 135A

5: 80 - 270A

6: 160 - 540A

0.1A

0.1A

0.1A

1A

1A

1A

1A

1A

2A

0.3A

1.2A

4.8A

10A

10A

20A

40A

80A

160A

F5A

Display the primary current if 5A

secondary CT's are used.

Function of size in F3

Function of size in F3

OFF (denotes

SAMMS sensors

in use)

F6

Select the service factor.

1 or 1.15

N/A

1.15

F7

Select the overload trip class.

2-23

1

10

F8

Enable/disable autoreset of overload

and external trips.

ON/OFF

N/A

OFF

F9

Enable/disable phase unbalance

protection.

ON/OFF

N/A

ON

F10

Display the time to wait until the motor

can be restarted. Applies after an

overload trip with the winding or

housing temperature above the

maximum allowed for restarting.

Real Time Value

1s

N/A

F11

Enable/disable the emergency restart

capability.

ON/OFF

N/A

OFF

Table 3.8 Motor control and protection functions (page 1 of 3)