3 Operating the SAMMS-LV Device

3. To change the protection setting, press the UP or DOWN

key to display ON or OFF, then press ENTER to select the

setting that is shown. The display blanks while the ENTER

key is pressed.

4. Return to Step 3 if you select an incorrect setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to step through to another function.

F23A Jam Pickup Current (SAMMS-LVX Only)

1. Press the LIST key to view the jam current pickup value in

use. The range of possible values is between 120% and

400% to the FLC, in increments of 5%. The factory default

is 200%.

2. To change the setting, you must be in program mode.

3. To change the setting, press the UP or DOWN key until the

desired setting is displayed then press the ENTER key to

select the setting. The display blanks while the ENTER key

is pressed.

4. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

5. Press the (F)unction key to step through to another function.

F24 - Loss of Load Protection or Warning

(SAMMS-LVX Only)

1. Press the LIST key to view the active loss of load setting (ON

or OFF). The factory default setting is warning (OFF), and the

other setting is protection (ON). This function is disabled for

five times the class time after starting or speed or direction

changes.

a. When protection (ON) is selected and the motor current

drops below the pickup current value, within 360 msec,

the External Trip LED will light and the SAMMS-LV trips.

b.When warning (OFF) is selected and the motor current

drops below the pickup current value within 360 msec,

the External Trip LED flashes but the SAMMS-LV does not

trip.

2. To change the setting, you must be in program mode.

3. To change the protection setting, press the UP or DOWN

key to display ON or OFF options, then press ENTER to

select the setting that is shown. The display blanks while the

ENTER key is pressed.

4. Return to Step 3 if you select an incorrect setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to step through to another function.

F24A - Loss of Load Pickup Current (SAMMS-LVX

Only)

1. Press the LIST key to view the active setting. The range of

possible values is between 20% and 95% to the FLC, in

increments of 5%. The factory default is 50%.

2. To change the setting, you must be in program mode.

3. To change the setting, press the UP or DOWN key until the

desired setting is displayed then press the ENTER key to

select the setting. The display blanks while the ENTER key

is pressed.

4. Return to Step 3 if you select an incorrect setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to go to other functions.

F25 - Percentage of Motor Winding Temperature

1. Press the LIST key to view the temperature of the motor

windings as a percentage of the steady-state, full-load

winding temperature. The maximum allowable winding tem-

perature percentage is 175%.

2. The UP, DOWN, and ENTER keys are disabled for this

function.

3. Press the (F)unction key to go to other functions.

F26 - Baud Rate

1. Press the LIST key to view the active setting. Allowable

settings are 2400, 4800, or 9600 baud. The factory default

is 4800.

2. To change the setting, you must be in program mode.

3. Press the UP or DOWN key to scroll through the range of

settings, until the selected setting appears on the display.

4. Press the ENTER key to change the active setting to the

selected setting. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the

new setting.

5. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to the display mode.

6. Press the (F)unction key to step through to another function.