3 operating the samms-lv device, 1 the (f)unction key, 2 the list key – Siemens MCC-3298 User Manual

Page 28: 3 up and down keys, 4 using the enter key

Advertising
background image

26

3 Operating the SAMMS-LV Device

3.27.1 The (F)unction Key

When you press the (F)unction key, the function mode is

selected and the HHC displays the number of the selected

function preceded by F. With the HHC in the function mode, use

the UP and DOWN keys to step from one function to the next.

3.27.2 The LIST Key

When you press the LIST key, the display mode is selected and

the HHC displays the value corresponding to the selected

function. If the selected function is a set point, the HHC displays

the actual setting. If the selected function is a measured

quantity, the HHC displays the value of the measured quantity.

In the display mode, use the UP and DOWN keys to step

through the range of possible set points for the selected

function. Pressing the LIST key returns the active setting to the

display.

There is one occasion when the LIST key is disabled making the

corresponding functions inoperative. In a SAMMS-LV device

with autoreset disabled at the factory, the LIST key has no effect

for F8.

3.27.3 UP and DOWN Keys

Use the UP and DOWN keys to step through the functions while

the HHC is in the function mode. When the HHC is in the display

mode, use the UP and DOWN keys to step through the values

for a selected function. You can use the keys in three ways:

1. Single step - press the key and release it.

2. Slow scroll - press the key and hold the key down for no

longer than two or three seconds.

3. Fast scroll - press the key and hold the key down long

enough for the HHC to step through more than five steps.

The following information discusses how to operate the UP and

DOWN keys in the function and display modes.

1. In the function mode, the UP key increases the function

number by one and the DOWN key decreases the function

number by one. If F0 appears on the display, pressing the

DOWN key rolls the function over to the highest-numbered

function, F27. If the highest-numbered function (F27) ap-

pears in the display, pressing the UP key rolls the function

over to the lowest-numbered function (F0).

2. In the display mode, use the UP and DOWN keys to step

through the range of settings for each set point function. You

also use the UP and DOWN keys to step through the

individual line currents and the average line current of F15.

Just as the UP and DOWN keys cause the function numbers

to roll over, they also cause the range of settings to roll over.

3.27.4 Using the ENTER Key

Use the ENTER key to change settings on the HHC display. The

SAMMS-LV device disables the ENTER key under the following

conditions:

1. The ENTER key is disabled while the device is in the function

mode.

2. The ENTER key is disabled for non-setting functions that

display a parameter.

3. The ENTER key is disabled while the motor is running to

prevent settings from being changed while the motor is

running.

Use the following procedure to change a setting. This example

shows you how to change the full-load current setting from

112A to 67A.

1. With the HHC in the program mode (see section 3.28.1),

press the (F)unction key. The display shows the number of

the function most recently selected, (e.g. F9).

2. Use the UP or DOWN key (as described above) to step or

scroll to the desired function. The display shows the desired

function, (e.g. F4).

3. Press the LIST key. The display shows the active setting for

the selected function, (e.g. 112, representing a full-load

current setting of 112A for a motor controlled by a size 4

contactor.)

4. Use the UP or DOWN key (as described above) to step or

scroll to the desired setting. The display shows the desired

setting, (e.g. 67 for 67A).

5. To enter the desired setting (67) which is displayed, press

the ENTER key. The display becomes blank while you hold

down the ENTER key and the SAMMS-LV device stores the

new setting.

6. Press the LIST key to show the new setting (67) on the

display.

7. To move to the other functions, press the (F)unction key. The

display shows, in the example, F4.

8. Press the UP and DOWN keys to step through the function

numbers. The SAMMS-LV device is in the function mode.

9. To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the

UP or DOWN key to change to display mode.

Advertising