SICLOCK

®

TC 400

6.3

Connecting the external synchronization

The signal of the connected radio clock is detected automatically and displayed
in the /Inputs/Input 1/Status (0.20.02) parameter (or /Inputs/Input 2/Status
(0.21.02) parameter).

Figure 6-2 Circuit diagram for a passive and an active radio clock

Table 6-1

Terminal assignment of the radio clock inputs

Terminal

Designation

X2-7

RADIO CLOCK GND

X2-8

RADIO CLOCK 1A

X2-9

RADIO CLOCK 1B

X2-10

RADIO CLOCK 2A

X2-11

RADIO CLOCK 2B

X2-8

X2-9

48 V

X2-7

passive

Radio Clock 1

X2-8

X2-9

48 V

X2-7

active

Radio Clock 1

passive

Radio Clock 2

X2-10

X2-11

48 V

X2-10

X2-11

48 V

active

Radio Clock 2

Note

If you are operating two radio clocks, connect the preferred model to RADIO
CLOCK 1.