SICLOCK

®

TC 400

9.2.5

Output telegram (for OUTPUT 1 to 3)

If the output signal is defined as a serial telegram, you can specify the settings for
the data transfer with the /Outputs/Output Telegram (0.19.01) parameter.

Format

The parameter entry /Outputs/Output Telegram/format (0.19.01) offers the follow-
ing telegram formats for selection:

• Meinberg compatible (including time zones)
• Meinberg compatible (not including time zones)
• NMEA (0183/ZDA)

Baud rate

You can set the following values with the parameter entry /Outputs/Output Tele-
gram/baud rate (0.19.01):

1200 Bd, 2400 Bd, 4800 Bd, 9600 Bd, 19200 Bd, 38400 Bd, 57600 Bd, 115200 Bd

Data width

You can specify the number of data bits with the parameter entry /Outputs/Output
Telegram/data bits (0.19.01):

7 bits or 8 bits

Parity

You can specify the parity with the parameter entry /Outputs/Output Tele-
gram/parity (0.19.01):

none, even, uneven

Stop bits

You can specify the number of stop bits with the parameter entry /Outputs/Output
Telegram/stop bits (0.19.01):

1 bit or 2 bits

Further information

OUTPUT 1 to 3 via terminals (Section 9.2.3)