Service – Lochinvar Copper-fin II/IIE 402 - 2072 User Manual

Page 19

Advertising
background image

1

Service

(continued)

19

Copper-fin II/IIE Boiler and Water Heater

Service Manual

DHW/SH switching time (boiler only)

The time that the SMART SYSTEM control services a DHW
demand before returning to the SH demand is set by this
parameter. The range of this parameter is 0 to 240 minutes.
Setting this parameter to 0 disables the switching function. The
default value of this parameter is 30 minutes.

DHW Tank offset (water heater only)

The tank offset is the number of degrees the DHW tank
temperature must go above the tank setpoint before the water
heater will turn off. The temperature range of this parameter is
0° to 10°F (5°C). The default value is 4°F (2°C).

DHW Tank differential

The tank differential is the number of degrees the DHW tank
temperature must go below the tank setpoint before the heater
or boiler will start to heat the DHW tank. The temperature
range of this parameter is 0° to 40°F (22°C). The default value
is 6°F (3°C).

Freeze protection pump on

In order to prevent the water in the heater from freezing, the
SMART SYSTEM control turns on the boiler pump whenever
the inlet temperature goes below the minimum temperature.
The range of this parameter is 32°F (0°C) to 104°F (40°C). The
default value is 45°F (7°C).

Freeze protection burner on

If the inlet temperature continues to drop after strating
the pump (see Freeze Protection Pump On), and the inlet
temperature goes below a second minimum temperature, the
first stage will fire. The temperature range of this parameter
is 32°F (0°C) to 104°F (40°C. The default value is 37°F (3°C).

Freeze protection differential

Once the pump has turned on, this parameter determines how
much the inlet temperature must rise before the pump turns
off. Similarly, once Stage 1 has turned on, this parameter also
determines how much the inlet temperature must rise before
Stage 1 turns back off. The temperature range of this parameter
is 0° to 72°F (40°C). The default temperature is 5°F (3°C).

DHW settings

DHW tank setpoint

When a temperature sensor is installed in the DHW tank, the
DHW tank setpoint sets the target temperature of the water
in the tank. The temperature range of this parameter is 60°F
(15°C) to 190°F (88°C). The default value is 120°F (49°C).

DHW boiler setpoint (boiler only)

When an indirect DHW call for heat becomes active, the control
will use the DHW boiler setpoint to determine the firing rate
of the unit based on the actual outlet water temperature. The
temperature range of this parameter is 32°F (0°C) to 261°F
(127°C). The default value is 180°F (82°C).

SH/DHW switching time (boiler only)

When a SH call for heat and a DHW call for heat are present at
the same time, the SMART SYSTEM control can switch back
and forth between the two calls. This parameter determines
the maximum length of time the boiler will service the SH call
before switching to the DHW call. The range of this parameter
is 0 to 240 minutes. Setting this parameter to 0 disables the
switching function. The control will service the DHW demand
until it ends, then return to the SH demand (if active). The
default value of this parameter is 30 minutes.