Troubleshooting – Lochinvar Copper-fin II/IIE 402 - 2072 User Manual

Page 41

Advertising
background image

3

Troubleshooting

(continued)

41

FAULT

DESCRIPTION

CORRECTIVE ACTION

Louver Proving

(Lockout will reset
automatically after

5 minutes or may be

reset immediately once

condition has been

corrected. Press the

RESET button on the

SMART SYSTEM display

to reset.)

An optional remote proving switch is not
making.

• Check function of remote devices.

Check for loose or misplaced jumper if

proving switch is not installed.

Tank Open

Sensors equipped with an internal limit (such
as the Lochinvar Squire

®

Indirect Tank), the

limit has opened due to temperature (195°F)
or the sensor has become disconnected.

• Check the tank temperature.

• Repair or replace the sensor wiring if damaged.

• Replace the sensor if necessary.

APS Open

(Lockout will reset

automatically after 5

minutes or may be

reset immediately once

condition has been

corrected. Press the

RESET button on the

SMART SYSTEM display

to reset.)

The air pressure switch did not make within
1 minute after the combustion air blower has
been energized.

• Check air filter. Clean or replace as necessary.

• Vent/air intake lengths exceed the maximum allowed
lengths.

• Check for blockage or obstruction in vent/air inlet pipe
or at terminations.

• Verify combustion air blower is operating. Replace if
necessary.

APS Closed

(Lockout will reset

automatically after 5

minutes or may be

reset immediately once

condition has been

corrected. Press the

RESET button on the

SMART SYSTEM display

to reset.)

The SMART SYSTEM control sensed that
the air pressure switch was closed before the
combustion air blower was energized.

• Check for jumper on air pressure switch.

• Check for an unusually high negative draft in the vent
stack.

Wrong ID Plug

Control module ID plug does not match the
Accept Personality Plug parameter.

• Verify that ID plug is connected properly to connector
X5 on the control module.

• Verify that the wiring in the ID plug is not cut or
damaged and that the wiring connectors are seated
properly in the plug.

• Verify that the number on the ID label on the control
panel matches the number in the Accept Personality
Plug
parameter. If not, replace the control module.

• When replacing control modules, verify that the
number in the Accept Personality Plug parameter
matches the number on the ID label (reference page
24 of this manual). If so, press the ENTER button on
the SMART SYSTEM display. If not, replace the
control module.

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

Copper-fin II/IIE Boiler and Water Heater

Service Manual