Service – Lochinvar Copper-fin II/IIE 402 - 2072 User Manual

Page 8

Advertising
background image

1

Service

8

General Operation

How the appliance operates

The Copper-fin uses a finned copper tube heat exchanger to
transfer heat from the flue products to the water. An electronic
control module monitors various inputs to initiate a call for
heat. The blower provides both primary and secondary air to
the burner and forces the flue products out of the combustion
chamber and into the vent system.

How the control module operates

The Copper-fin control module receives input from appliance
sensors. The control module activates and controls the
blower and gas valves to regulate heat input and switches
heater, DHW and system pumps on and off as needed. The
user/installer programs the module to meet system needs by
adjusting control parameters. These parameters set operating
temperatures and heater operating modes. Appliance operation
can be based on heater outlet water temperature, heater return
water temperature, system supply temperature, system return
temperature or tank temperature, depending on the parameter
setting.

Sequence of operation

Table 1A shows control module normal sequences of operation
for space heating and DHW operation. The combined operation
sequence is for a typical application, programmed to provide
DHW priority.

Access modes

User

The user can adjust space heating and/or tank setpoints using
the UP and DOWN buttons at any time during normal
operation. By entering the USER code (0704), the user can also
change temperature units, time and date, and night setback
settings. In user mode, the following parameters can be viewed
but not changed: Heater outlet water temperature in DHW
mode; heater model number; software version; total operating
hours, and total cycles.

Installer

Most parameters are available only to the installer, accessible
only by entering the installer access code (5309).

Saving parameters

To save parameters and exit programming:

Press the ENTER/RESET button, then the MENU/EXIT button
3 times.

To keep parameter settings only for a current operating cycle:

Press the MENU/EXIT button 3 times after making all desired
parameter changes.

To enter a parameter and continue programming:

Press the MENU/EXIT button 1 time to return to the parameter
listings; press again to return to the menu listings. Remember
to press the ENTER/RESET button when finished programming
in order to save the changes made.

Copper-fin II/IIE Boiler and Water Heater

Service Manual

Advertising