Troubleshooting – Lochinvar Copper-fin II/IIE 402 - 2072 User Manual

Page 42

Advertising
background image

3

Troubleshooting

42

FAULT

DESCRIPTION

CORRECTIVE ACTION

Temp O/Shoot

(Lockout will reset

automatically after 5

minutes or may be

reset immediately once

condition has been

corrected. Press the

RESET button on the

SMART SYSTEM display

to reset.)

The temperature rise across the heat
exchanger has exceeded the set parameters
for the appliance.

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the appliance is piped properly into the
heating system. Refer to the Water Connections
Section
of the Installation and Operation Manual for the
proper piping methods.

• Check for 120 VAC to the pump motor on a call
for heat. If voltage is not present, check the wiring
leading to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the
pump is not operating, replace the pump.

Outlet water temperature has exceeded the
maximum outlet water temperature.

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the appliance is piped properly into the
system. Refer to the Water Connections Section of
the Installation and Operation Manual for the proper
piping methods.

• Check 120 VAC to the pump motor on a call for heat.
If voltage is not present, check wiring leading to the
main control board. Replace the main control board
if

necessary.

• If 120 VAC is present on a call for heat and the pump
is not operating, replace pump.

• Replace the main control board.

Rem Ctrl Flt

External control is cycling too often.

• Check setpoint of the external control.

• Check the wiring between the external control and
the

unit.

• Replace the control.

Parameters Progr

(Will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM

display

to reset.)

After downloading parameters from a laptop,
the main control board must be reset.

• Press the ENTER/RESET button on the Smart
System display panel.

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

Copper-fin II/IIE Boiler and Water Heater

Service Manual