Copper-fin II/IIE Boiler and Water Heater

Service Manual

Access to the burners will require the following steps:

1. Turn off main electrical power to the appliance.

2. Turn off main manual gas shutoff to the appliance.

3. Remove the upper and lower outer front access doors.

4. Disconnect the manifold(s) from the gas train using the

union(s) just below each gas valve.

5. Disconnect the wiring to the hot surface igniter(s) and
ground.

6. Disconnect burner pressure line at burner.

7. Remove the screws from the manifold mounting bracket(s)

and remove the manifold(s).

8. Remove the screws from the burner mounting flanges and

slide the burner(s) out toward the front of the unit. Use

caution to prevent damage to the burners, refractory, hot

surface igniter, and wiring.

9. Remove soot from the burners with a stiff bristle brush.

Dirt may be removed from the burner ports by rinsing the

burner thoroughly with water. Drain and dry burners

before re-installing. Damaged burners must be replaced.

10. Reassemble in reverse order.

When installed in a dusty and dirty location,
the burners may require cleaning on a 3 to 6
month schedule or as needed, based on the
severity of contamination. Contaminants
can be drawn in with the combustion air.
Non-combustible particulate matter such as
dust, dirt, concrete dust, or drywall dust can
bloc burner ports and cause non-warrantable
failure. The standard inlet air filter will help
eliminate dust and dirt from entering the
unit.

NOTICE

While burners are removed, check the heat
exchanger surface for sooting. If present, the
heat exchanger must be cleaned. Reference
the Heat Exchanger Cleaning procedures in
this manual.

NOTICE

Checking combustion air pressure

The combustion air fans are factory pre-set and should not
require adjustment in most cases. Follow the steps in the
Checking / Adjusting Combustion Air Pressure Section to adjust
the fan if a continuous Low Air status code occurs.

On the 399,999 - 750,000 Btu/hr models,
the air shutter is adjusted to the side of the
fan as depicted in FIG. 2-2. On the 990,000
- 2,070,000 Btu/hr models, the air shutter is
adjusted by sliding the arm located on the
front of the air box as depicted in FIG. 2-3.

NOTICE

Check for proper installation and draft in the venting system
prior to any adjustments. Correct as needed.

AIR SHUTTER

LESS AIR

MORE AIR

Figure 2-2_Adjusting air shutter - 399,999 - 750,000 Btu/
hr Models

AIR SHUTTER
ADJUSTING BRACKET

LESS AIR

MORE AIR

Figure 2-3_Adjusting air shutter - 990,000 - 2,070,000
Btu/hr Models