FAULT

CAUSE

CORRECTIVE ACTION

Noisy

Operation

- Gas supply problem.

• Refer to the Gas Connections Section of the

Installation and Operation Manual for detailed
information concerning the gas supply.

- Gas/air mixture problem.

• Refer to the Checking Manifold Gas Pressure and

Combustion Analysis Procedure on pages 29 and 30 of
this manual for the proper settings. Verify
that the vent/air intake lengths do not exceed the
maximum listed in the Venting section of the
Installation and Operation Manual.

- Dirty/damaged burner(s).

• Refer to pages 28 and 29 in this manual for the burner
removal and inspection procedure. Clean or replace the
burner as necessary.

- Low water flow through the heat exchanger. • Refer to the Water Connections Section of the

Installation and Operation Manual for

minimum flow rates. Verify that the appliance is piped in
a primary/secondary fashion and that the appliance and
system pump are running on a call for heat.

- Air in the piping system.

• Properly purge all air from the piping system.

- Low system water pressure.

• Verify system pressure is a minimum of 12 PSI.

No Pump

Operation -

Boiler Pump

System Pump

or

DHW Pump

- Faulty pump relay.

• Replace relay.

- Faulty pump.

• Replace pump.

- Internal fault on control board.

• Check fuse F5.


• Replace main control board.

Note: Make sure the boiler pump horse power (hp) does
not exceed 1 hp.

Relief Valve

Opening

-

System pressure exceeds relief valve

setting.

Lower the system pressure below the rating of

the supplied relief valve or replace the standard relief
valve with a higher rated valve up to the maximum
pressure of the heat exchanger.

- Improperly sized expansion tank.

• Install properly sized expansion tank.

- Outlet water temperature in excess of 210°.

• Check setpoint of temperature control.

• Check temperature rise across heat exchanger. Refer to

the temperature rise chart in the Water

Connections Section of the Installation and Operation
Manual.

Table 3D Troubleshooting Chart - Noisy System

Copper-fin II/IIE Boiler and Water Heater

Service Manual