Maintenance, Maintenance and annual startup service technician, Owner maintenance – Lochinvar Copper-fin II/IIE 402 - 2072 User Manual

Page 25

Advertising
background image

2

Maintenance

25

Maintenance and annual startup

Service technician

(see the following pages for instructions)

General:

• Address reported problems

• Inspect interior; clean and vacuum if

necessary;

Check for leaks (water, gas, flue,

condensate)

• Examine venting system

• Check system water pressure/system

piping/expansion

tank

• Check control settings

• Check igniters

• Check wiring and connections

• Check flue gas passageways

• Flame inspection (stable, uniform)

Inspect and clean the burners

• Check manifold gas pressures

Perform start-up checkout and

performance verification per the Startup

Section in the Installation and Operation

Manual.

If combustion or performance
indicate need:

• Clean heat exchanger with a stiff bristle

brush


Remove and clean burners using

water. Dry before re-assembling.

• Clean the blower wheel with a brush and

vacuum. Do not let dirt from cleaning get
pulled into the blower.

ANNUAL START-UP

Owner maintenance

(see the User’s Information Manual for instructions)

Daily

• Check appliance area

Check pressure/temperature

gauge

Monthly

• Check vent piping

• Check air piping

• Check relief valve

• Replace combustion air filter

Note: More frequent replacement may
be necessary in dirty environments.
Do not use pleated filters.

Periodically

• Test low water cutoff (if used)

• Reset button (low water cutoff)

Every

6 months



• Check appliance piping (gas and

water) for leaks

• Operate relief valve

End

of season

months

Shut appliance down (unless

boiler used for domestic hot

water)

Table 2A_Service and Maintenance Schedules

Copper-fin II/IIE Boiler and Water Heater

Service Manual