Troubleshooting and repair, Main transformer test (continued), Warning – Lincoln Electric POWER MIG SVM167-A User Manual

Page 48

Advertising
background image

TEST PROCEDURE

THE ON/OFF POWER SWITCH will be
“hot” during these tests.

NOTE: Secondary voltages will vary

proportionately with the primary
input voltage.

1. Disconnect the main input power

supply to the machine.

2. Remove the case top and side panels

with a 3/8” nutdriver.

3. Remove the tool tray with a 5/16” nut

driver.

4. Locate leads X2 thru X8 located on

the output selector switch. See Figure
F.1.

5. Locate lead X1 located on the output

rectifier assembly. See Figure F.2.

6. Locate leads X9 and X10. See Figure

F.3.

7. Connect main input power to the

machine.

8. Turn the POWER MIG 215 ON/OFF

Power Switch to the ON position.

9. Carefully make the following voltage

tests. See Table F.1.

10. Turn off the machine.

11. If any of the voltages are incorrect

or missing, check for loose or broken
connections

between

the

main

transformer and the test points.

TROUBLESHOOTING AND REPAIR

F-12

F-12

POWER MIG® 215

MAIN TRANSFORMER TEST (continued)

FIGURE F.1. – OUTPUT SELECTOR SWITCH TERMINALS

WARNING

ELECTRIC SHOCK can kill.

• Do not touch electrically live

parts such as output terminals
or internal wiring.

• All input power must be electri-

cally disconnected before pro-
ceeding.

WARNING

X8

X7

X6

X5

X4

X3

X2

Return

to

Section

T

OC

Return

to

Section

T

OC

Return

to

Section

T

OC

Return

to

Section

T

OC

Return

to

Master

T

OC

Return

to

Master

T

OC

Return

to

Master

T

OC

Return

to

Master

T

OC