MACH® Series

Gas-Fired Boiler

Installation

Page 14

Pipe Capacity for Natural Gas

Equivalent Pipe Length

Maximum Capacity in Cubic Feet of Natural Gas per Hour

Pressure Drop of 0.5 inch Water Column/Equivalent Length of Pipe

(in feet)

Nominal

Iron Pipe

Size

(Inches)

Internal

Diameter

(Inches)

90º Ell

(Feet)

Tee

(Feet)

20

40

60

80

100

150

200

1/2 0.622 1.55

3.1 120 82 66 57 50 40 35

3/4 0.824 2.06

4.12 250 170 138 118 103 84 72

1 1.049 2.62

5.24 465 320 260 220 195 160 135

1- 1/4

1.380

3.45

6.9

950 660 530 460 400 325 280

1- 1/2

1.610

4.02

8.04 1460 990 810 690 620 500 430

2

2.067

5.17

10.3

2750 1900 1520 1300 1150 950 800

2- 1/2

2.469

6.16

12.3

4350

3000 2400 2050 1850 1500 1280

3

3.068

7.67

15.3

7700 5300 4300 3700 3250 2650 2280

4

4.026

10.1

20.2 15800

10900 8800 7500 6700 5500 4600




3.7.1 Gas Supply Piping by Installer

The boiler and all gas piping connections should be
pressure-tested and must be checked for leaks before
being placed into service. Test with compressed air or
inert gas if possible.

The boiler must be disconnected at the boiler manual
shut-off valve (located at the end of the supplied gas
train) from the gas supply piping system during any
pressure testing of the system at pressures in excess of
1/2 psig (14" W.C.).

During any pressure testing of the gas supply piping
system at pressures equal to or less than 1/2 psig (14"
W.C.), the boiler should be isolated from the gas
supply piping system by closing the manual shut-off.

Some leak test solutions, including soap and water,
may cause corrosion. These solutions should be
rinsed-off with water after testing.

3.8

B

OILER

W

ATER

P

IPING

3.8.1 Piping Design

Water Flow in System

For proper water flow requirements see below.
Incorrect flow may result in eventual damage or
premature failure of the equipment.

Model Max

Flow

GPM

Min Flow

GPM

DP ft. at

max flow

1050 105 52 12

900 90 45 12

750 75 37 12

450 45 22 8.5

300 30 15 8.5


Contact factory for minimum flow at other than
maximum firing rate.