MACH® Series

Gas-Fired Boiler

Parts and Technical Support

Page 37

6.1

W

IRING

D

IAGRAMS


6.1.1 Terminal Block Assignments – High Voltage Circuit (TB2)

Terminal Number

Label

Description

1

115 VAC LINE

2

115 VAC NEUTRAL

Boiler Supply Power, 115 VAC, 60 HZ, 1 ph, 8 amp

3

115 VAC NEUTRAL

Aux. Switched Output

4

115 VAC NEUTRAL

Boiler Circ. Pump

5

115 VAC NEUTRAL

DHW Circ. Pump

6 GROUND

Boiler

Supply

Ground

7 GROUND

8 GROUND

Aux .Ground

9

115 VAC SW. OUTPUT

Aux. Switched Output, Pilot duty only, 1 amp max.

10

115 VAC CIRC. PMP
CONTACTOR

Boiler Circ. Pump, Pilot duty only, 1 amp max.

11

115 VAC DHW PMP
CONTACTOR

DHW Circ. Pump, Pilot Duty only, 1 amp max.

12

MASTER ALARM RELAY

13

MASTER ALARM RELAY

Dry Contacts, 24 VAC max, 1 amp max.

14

THREE WAY VALVE RELAY

15

THREE WAY VALVE RELAY

DHW Dry Contacts, 24 VAC max, 1 amp max.

16 DAMPER

RELAY

17 DAMPER

RELAY

Combustion Air Damper, Dry Contacts, 24 VAC max, 1 amp
max.