MACH® Series

Gas-Fired Boiler

Maintenance

Page 35

5.5.2 Auto-reset Service Codes

Code Lockout

Description

b 08

Air pressure switch open.

The air pressure switch failed to close to indicate sufficient air flow to start the boiler.

b 18

Outlet high limit temp.

The outlet water temperature has exceeded the internal high limit temperature setting.

b 19

Return high limit temp.

The return water temperature has exceeded the internal high limit temperature setting.

b 24

Switched inlet / outlet.

The inlet water temperature has been more than 18° F above the outlet for more than
75 seconds.

b 25

Outlet temp rapid change.

The outlet water temperature is increasing too fast. Indicating low flow condition.

b 26

High exhaust back pressure.

The high exhaust back pressure switch is tripped indicating a blocked stack, inlet, or
condensate system.

b 30

Max delta T.

The temperature rise across the heat exchanger is greater than maximum allowed,
indicating insufficient flow.

b 40

Flue sensor open.

The flue gas temperature sensor is indicating an open circuit.

b 52

High flue temp.

The flue temperature has exceeded the maximum allowable setting.

b 61

Air pressure switch closed.

The air pressure switch failed to open prior to starting the blower.

b 65

Fan speed incorrect.

The fan is being directed to a higher speed than it is achieving.

WARNING

If any “Manual Reset” limit device trips,

DO NOT

reset without determining and correcting the cause.