MACH® Series

Gas-Fired Boiler

Installation

Page 20

3.12

I

NITIAL

A

DJUSTMENTS

3.12.1 Operating Temperature Controller

The MACH boiler is equipped with a combination
combustion and temperature control. This control
monitors combustion and lighting of the boiler, as well
as maintaining temperature of the supply water. The
temperature control portion modulates the boiler to
maintain the desired outlet temperature based on the
selected operating configuration.

CAUTION!

The user should become thoroughly familiar with
the operation of the boiler and controls before
attempting to make any adjustments.

3.12.1.1 Operation of the Control

The boiler is operated through the control/display
panel. The display has 3 modes of standard operating
menus. The modes are:

• Standby mode will display (Stby)
• Parameter mode will display (PArA)
• Information mode will display (InFo)


At each level the keys and the display have different
functions. To ascertain which mode you are in, the
displayed information will be shown as indicated
under “display”.

Mode Description Display Example

Standby

(

Stby)

Normal display

mode

1st digit

without a dot

0 180

Parameter

(

PArA

)

Parameter

settings

1st digit with

a dot

1.125

Information

(

InFo

)

display boiler

sensors

1st digit with a

blinking dot*

1.180*


Standby Mode:

The display defaults to this mode at startup or reset of
the control. If no key is pressed for 20 minutes the
display will return to this mode. The function of the
keys may be two-fold as shown below.

Key(S) Duration

Function

Mode

momentary

Change to next mode

Reset

momentary

Reset the control

Plus momentary

Show the comfort heat

setpoint, or max setpoint

(outdoor reset only)

Plus

long*

Turn the comfort heat system

on or off

Minus momentary

Show the domestic hot water

setpoint

Minus long*

Turn the domestic hot water

system on or off


*Note: Long duration is greater than 2 seconds.

When in the Standby Mode the control indicates
boiler status with the first digit of the display. The
remaining digits indicate the boiler's actual
temperature or lockout code. The following table
indicates the meaning of the display digits when in
the standby level.

First Digit

Boiler Status

0

Burner off - No call for heat

1

Pre purge or post purge

2 Ignition

3

Burner on in Comfort Heat mode

4

Burner on in Domestic Hot Water mode

5

Checking the airflow switch

6

Burner off - An internal setpoint has been
reached. System is still calling for heat.

7

Burner off - Comfort Heat pump running on