4.2.3 Emergency Shut-Off


The main gas cock should be closed immediately if an
emergency situation occurs.

4.3

T

YPICAL

B

OILER

O

PERATING

C

ONDITIONS

Natural Gas

*(1030 Btu/cu. ft.)

LP Gas

**(2500 Btu/cu. ft.)

Model

Number

Input

Rating

(Btu/hr)

Gas

Rate

(CFH)

Output

Capacity

(Btu/hr)

Gas

Rate

(CFH)

Output

Capacity

(Btu/hr)

Total

Amperage

300

300,000

291*

275,000

120**

275,000

8 amps or less

450

450,000

437*

414,000

180**

414,000

8 amps or less

750

750,000 728* 712,500

300*

712,500

8 amps or less

900

900,000

873*

846,000

360**

846,000

8 amps or less

1050

1,050,000

1019*

987,000

420**

987,000

8 amps or less


Note: The heat exchanger is constructed and stamped for 50 psig maximum operating pressure and/or 200º F
maximum temperature.

Main Gas Cock

WARNING!

If overheating occurs or the gas supply
fails to shut off, do not turn off or
disconnect the electrical supply to the
pump. Instead, shut off the gas supply at a
location external to the boiler.

Emergency Shut-Off