Patterson-Kelley MACH-05 User Manual

Page 58

Advertising
background image

Parameter Settings for MCBA Controls

No.

Description

Lower Limit

Upper Limit

Installed

MCBA

Parameter

Settings

MACH

1050 PK

Factory

Setting

for MCBA

MACH

300 PK

Factory

Setting

for MCBA

MACH

450 PK

Factory

Setting

for MCBA

MACH

750 PK

Factory

Setting

for MCBA

MACH

900 PK

Factory

Setting

for MCBA

27

DHW detection hysteresis Off

-36 F

54 F

5

5

55555555

28

Restart delay CH x 10.2 seconds

0 seconds

30 x 10.2 seconds

3

3

33333333

29

Restart delay DHW x 10.2 seconds

0 seconds

30 x 10.2 seconds

3

3

33333333

30

Restart delay DHW to CH

0 = switch with burner On

3

3

33333333

1 x 10.2 seconds

30 x 10.2 seconds

31

Difference T1-T2 for modulating back

9

F

7

2

F

4

64

6

4

64

64

64

64

64

64

64

6

32

RMCI address

-1 = RMCI Of

f

-1

-1

-1

-1

-1

-1

-1

-1

-1

-1

33

Setvalue addition for DHW, Parameter 1

0 F

(194- par 1) F or 54 F

3

0

3

0

3

0

3

0

3

0

3

0

3

0

3

0

3

0

3

0

34

CH Heat Request Type

00

00

00

00

00

00

00

00

00

00

(1st digit) 2nd CH-circuit

0X = 2nd CH-circuit of

f

X

X

X

X

X

X

X

X

X

X

1X = 2nd CH-circuit slave

2X = 2nd CH-circuit maste

r

3X = 2nd CH slave, Tset depends on potmete

r

4X = 2nd CH master, Tset depends on potmeter

5X = 2nd CH- circuit slave,during DHW

6X = 2nd CH- circuit master, during DHW

7X = 2nd CH slave, during DHW,Tset depends on potmeter

8X = 2nd CH master, during DHW,Tset depends on potmeter

(2nd digit) CH Heat Request Type

X0 = Room Thermostat

X

X

X

X

X

X

X

X

X

X

X1 = Outside Temperature

X2 = 0 - 10 V on MCBA: Capacit

y

X3 = 0 - 10 V on MCBA: Temperature

X4 = 0 - 10 V on AM4: Capacit

y

X5 = 0 - 10 V on AM4: Temperature

X6 = +/- Control

35

DHW

13

13

13

13

13

13

13

13

13

13

Type (2nd digit)

X0 = Instant water heater with NTC

3

X1 = Instant water heater without NTC

3

X2 = Storage tank with NTC3

X3 = Storage tank without NTC3

X

X

X

X

X

X

X

X

X

X

X4 = Instant water heater+NTC3+anticondensation

X5 = Instant water heater +anticondensation

X6 = Storage tank+NTC3+anticondensation

X7 = Storage tank+anticondensation

X8 = Plate heat exchange

r

X9 = External heat request (by RMCI

)

DHW: 3 Way Valve or Pump (1st digit)

0X = 3 way valve normally ope

n

1X = Hot water pump

X

X

X

X

X

X

X

X

X

X

Advertising