Patterson-Kelley MACH-05 User Manual

Page 38

Advertising
background image

MACH® Series

Gas-Fired Boiler

Maintenance

Page 34

5.5.1 Manual Reset Service Codes

Code Lockout

Description

E 00

False flame.

A flame signal is present when it shouldn’t be.

E 02

Flame failure.

The burner did not light on startup, or loss of flame during run.

E 03

Gas Valve error.

Check all gas valves electrical connections.

E 04

General lockout.

The power was lost after a lockout. The control loses the description of the lockout on
power loss.

E 05

Internal control failure.

Call for service.

E 06

Internal control failure.

Call for service.

E 07

Internal control failure.

Call for service.

E 08

Air pressure switch open.

The air pressure switch failed to close to indicate sufficient air flow to start the boiler.

E 11

Internal control failure.

Call for service.

E 12

External limit open.

One of the external limits has opened. (High/Low Gas Pressure, High Temp, Low water).

E 13

Internal control failure.

Call for service.

E 14

Internal control failure.

Call for service.

E 15

Internal control failure.

Call for service.

E 16

Internal control failure.

Call for service.

E 17

Internal control failure.

Call for service.

E 18

Outlet high limit temp.

The outlet water temperature has exceeded the internal high limit temperature setting.

E 19

Return high limit temp.

The return water temperature has exceeded the internal high limit temperature setting.

E 25

Outlet temp rapid change.

The outlet water temperature is increasing too fast. Indicating low flow condition.

E 28

No blower feedback.

The blower should be running but it is not, or the feedback signal has been interrupted.

E 29

Blower feedback will not zero. The blower will not go to zero speed even though it should be off.

E 31

Outlet sensor shorted.

The outlet temperature sensor is short circuited.

E 32

Return sensor shorted.

The return temperature sensor is short circuited.

E 33

DHW sensor shorted.

The DHW temperature sensor is short circuited.

E 35

Flue sensor shorted.

The flue gas temperature sensor is short circuited.

E 36

Outlet sensor open.

The outlet temperature sensor is indicating an open circuit.

E 37

Return sensor open.

The return temperature sensor is indicating an open circuit.

E 38

DHW sensor open.

The DHW sensor is indicating an open circuit.

E 40

Flue sensor open.

The flue gas temperature sensor is indicating an open circuit.

E 44

Internal control failure.

Call for service.

E 52

High flue temp.

The flue temperature has exceeded the maximum allowable setting.

E 60

Internal control failure.

Call for service.



Note: When an Internal Control Failure occurs, as identified by E-Codes listed above, the failure is internal to the
MCBA and replacement of the MCBA is required. A qualified service technician must be called to replace the
MCBA device.