Internal Setpoint:

The internal setpoint is set with parameter 4. The
boiler temperature control modulates the boiler to
maintain this internal setpoint. The upper and lower
temperature differentials are used to instruct the boiler
at what temperature to turn on and at what temperature
to turn off.

Item Parameter

Value

Allowable

Range

Setpoint 4

160

68-185

Low Temp. Differential

22

10

0-36

High Temp. Differential

23

9

0-36

Low Temp. Setpoint

5

68

59-140

The boiler will modulate to try to maintain 160° F. If
the temperature increases above 169° F which is the
setpoint 160° F + High Temp Differential 9°F the
boiler will shut off. Once it shuts off it will not restart
until the temperature drops below 150° F which is the
setpoint – Low Temp Differential. The Low Temp Set
Point will not permit the operator to adjust the setpoint
below 68° F. (See graph below.)

Internal Setpoint

145

150

155

160

165

170

175

0

10

20

30

40

Time

Boiler Temperature

Boiler Set Point

Boiler Turns On

Boiler Turns Off

Domestic Priority:

If an indirect domestic hot water (DHW) tank is
connected, the DHW function of the boiler will
activate when the DHW temperature controller
(supplied by others) closes (Terminal 5 to 8 TB 1,
refer to Section 6.1.1), indicating a call for heat from
the DHW system. The parameters should be set as
follows:

Item Parameter

Value

DHW Setpoint

1

140

DHW Setpoint Addition

33

30

DHW Status

2

1

DHW High Temp. Differential

25

6

DHW Low Temp. Differential

24

6

DHW Options

35

13


In the above example, the boiler temperature will be
set to the DHW Setpoint + the DHW Setpoint
Addition (140ºF + 30ºF = 170ºF) when the DHW
temperature controller indicates a call for heat from
the DHW system. When the DHW system calls for
heat, the Central heat pump output (Terminal 10
TB2) de-energizes and the DHW pump output
(Terminal 11 TB2) energizes providing 120 VAC
power is provided to energize a relay coil for the
DHW pump. The DHW status should be set to 1
(DHW system ON).