Outdoor wiring, 12 outdoor wiring, Sensaphone – Phonetics 1108 User Manual

Page 24

Advertising
background image

Sensaphone

®

Model 1108 User’s Manual

12

Example with multiple
sensors connected to
Input 5. Alert condition
occurs when a normally
open switch closes.

2

3

4

5

6

7

8

1

GND

GND

GND

GND

Figure 2-9. Multiple Normally Open Sensors

2.12 Outdoor Wiring

When wiring sensors outdoors, DO NOT allow exposed wires
to run freely in open air; under such conditions, the Model
1108 is susceptible to serious damage during a lightning storm.
Depending upon the distance outdoor wiring must travel,
consideration should be given to use of shielded wire inside a
metal conduit. Both shield and conduit should be connected to
earth ground. This prevents stray voltage from entering the
unit.

sensor

Model 1108

Figure 2-10. Potential Sensor Damage from Stray Electrical Noise