High & low temperature limits, 4 establishing high and low temperature limits, Chapter 5: alarm programming 55 – Phonetics 1108 User Manual

Page 67: Press the corresponding input key (1 to 8), Fahrenheit, or from –30, F for low temperature and 100, F for high temperature, Press set, Press temp limits

Advertising
background image

Chapter 5: Alarm Programming

55

3.

Press the corresponding input key (1 to 8).

RECOGNITION

TIME

7

4

1

VOICE

REPS

2

8

INTERCALL

TIME

3

MAX CALLS

CALL

DELAY

CLOCK

TEMP LIMITS

5

CALIBRATE

6

The Model 1108 recites the programmed Recognition
Time for that input.

5.4 Establishing High and Low Temperature Limits

High and low temperature limits can be separately programmed
for each input configured as temperature. Limits can range
from
–20

°

to +150

°

Fahrenheit, or from –30

°

to 65

°

Celsius.

When temperature limits exceed high or low settings, the
Model 1108 will dial out with an alarm message. Default
settings are: 10

°

F for low temperature and 100

°

F for high

temperature.

5.4.1 Programming Temperature Limits

for a Selected Input

1.

Press SET.

SET

#

2.

Press TEMP LIMITS.

TEMP LIMITS

5

3.

From the number keys, press a number (from 1 to 8) that
corresponds to the temperature input being programmed.

RECOGNITION

TIME

7

4

1

VOICE

REPS

2

8

INTERCALL

TIME

3

MAX CALLS

CALL

DELAY

CLOCK

TEMP LIMITS

5

CALIBRATE

6

The Model 1108 responds: “Enter low temperature
limit.”