Installation, 32 mi – RayTek MI Miniature Infrared Sensor User Manual

Page 40

Advertising
background image

Installation

 

32 

MI 

For an installation of  two or more sensors in a RS485 network, each 
sensor is wired parallel to the others. 
You  may  connect  up  to  32  units.  Make  sure  to  deactivate  the  preset 
shunt resistor for all units except for the last one. The position of the 
switch to deactivate the shunt you can see on the electronic board in 
the figure above. 

Before units are in a network the multidrop address needs 
to be defined. Each sensor must have a unique address! 

The following figure illustrates the wiring of sensors in a  multidrop 
installation. 
 

Figure 22: Wiring the RS485 Network 

The  address  setting  can  be  done  either  through  buttons  or  through 
software alternatively

.

 

Addressing through Buttons 
Press  the  <Mode>  button  until  “M”  becomes 
visible.  Use  the  <Down>  and  <Up>  buttons 
until  the  requested  address  appears.  Press  the 
<Mode> button to acknowledge your selection. 
 

Addressing through Software 
Alternatively  the  sensor  can  be  controlled  by  means  of  the  optional 
available software DataTemp MultiDrop. 

RxB
RxA

RS232/485

Adapter

unit 1

unit

before

last

last unit

with shunt

activated!

unit 2

A

A

A

A

B

B

B

B