4 technical data table – Roberts Gorden COMBAT CTU 22 TO 115 User Manual

Page 14

Advertising
background image

COMBAT

®

CTU U

NIT

H

EATERS

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

8

4.4 Technical Data Table

Appliance Category II

2H/L 3B/P

Model

CTU-22 CTU-30 CTU-35 CTU-40 CTU-50 CTU-60 CTU-75 CTU-90 CTU-100 CTU-115

Heat Input

Gross CV

kW

(Btu/h) x (1000)

27
93

33

113

39

133

48

163

61

210

70

238

95

324

111

378

119

405

134
459

Heat Input

Net CV

kW

(Btu/h) x (1000)

25
84

30

102

35

119

43

147

55

189

63

215

86

292

100

341

107
365

121
414

Approximate

Heat Output

kW

(Btu/h) x (1000)

23
78

27
92

32

109

39

133

51

174

58

198

78

266

91

310

98

334

111

379

Thermostat Limit Thermodisc

CTUA, B/C, D

°C

75

75

75

75

75

75

75

75

75

75

Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG) Min. 17 mbar (6.8 in WG) Max. 25 mbar (10 in WG)

Burner Pressure

mbar

8.3

8.7

8.5

9.4

9.3

8.5

6.1

6.0

6.2

6.3

Gas Rate

m

3

/h

ft

3

/h

2.6

92

3.2

112

3.7

131

4.5

160

5.8

206

6.6

234

9.0

319

10.5

371

11.3
398

12.8

451

Natural Gas (G25) Data - Inlet Pressure 25 mbar (10 in WG) Min. 20 mbar (7.8 in WG) Max. 30 mbar (12 in WG)

Burner Pressure

mbar

12.2

12.7

12.5

14.0

13.6

13.2

9.2

9.3

9.2

10.2

Gas Rate

m

3

/h

ft

3

/h

3.03

107

3.33

117

4.31

152

4.78

169

6.14

217

6.98

247

9.49

335

11.06

391

11.86

419

13.43

474

LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (14.6 WG) Min. 25 mbar (10 in WG) Max. 45 mbar (18 in WG)
Alternative where permitted 50 mbar (20 in WG) Min. 42.5 bar (17 in WG) Max. 57.5 mbar (23 in WG)

Burner Pressure

mbar

26.6

24.9

25.4

25.9

25.6

26.8

25.6

27.3

25.3

25.9

Gas Rate

m

3

/h

kg

3

/h

liquid/h

1.01

1.87

3.7

1.23

2.28

4.5

1.48

2.75

5.4

1.77

3.27

6.4

2.27
4.21

8.3

2.58
4.79

9.4

3.51
6.50
12.8

4.09

7.58

14.9

4.39
8.13
16.0

4.97
9.21
18.1

LPG Gas Butane (G30) Data - Inlet Pressure 29 mbar (11,4 in WG) Min. 20 mbar (7.8 in WG) Max. 35 mbar (13.8 WG)

Burner Pressure

mbar

18.9

17.4

17.8

19.5

18.4

19.0

18.3

19.4

18.3

18.7

Gas Rate

m

3

/h

kg

3

/h

liquid/h

0.76

1.86

3.2

0.93
2.27

4.0

1.06

2.59

4.5

1.34

3.26

5.7

1.72

4.19

7.3

1.95

4.77

8.3

2.65
6.47

11.3

3.09

7.55

13.2

3.32
8.09
14.1

3.75
9.17
16.0

Gas rates corrected to standard conditions 1013.25 mbar 15° C.