34

15.3 Troubleshooting for Flame Supervision System

Repair or replace as

necessary.

Control box faulty.

Replace with correct type.

Use section 15.1 to

trace the fault.

Heater Operating

TROUBLESHOOT ENDS.

No

Repair or replace as

necessary.

Is inlet burner gas pressure

correct? Is live and neutral

polarity correct? Is

flame probe circuit correct?

Is there a current flowing in the

flame probe circuit with no

flame present?

Yes

No

Does “lockout” occur when

there is a flame present?

Yes

Is the connecting lead

damaged? Is the flame probe

damaged or touching earthed

components?

No

Is the green light on and

at least 1 µA DC flame

current?

Connect a DC ammeter in

series with the flame probe.

Yes

No

Yes

Yes

No

START

If problems persist, contact

ROBERTS GORDON

®

at

Tel: +44(0) 121 506 7709

www.rg-inc.com

NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.

15.4 Troubleshooting for Solenoid Valves

Valve faulty.

Replace with one of

correct type.

Fault elsewhere

Fault elsewhere

Valve Operating

TROUBLESHOOT ENDS.

No

Yes

Valve faulty.

Replace with one of

correct type.

Does gas pressure at

outlet of valve return to zero or

lower when valve turns off?

No

Yes

Does gas pressure at outlet

of the valve rise when

valve turns on?

No

Yes

Is gas pressure at inlet of the

valve correct for gas type?

Note pressure found.

No

Yes

START

Is 230 V at the valve

terminals at the

appropriate time.

Yes

No

If problems persist, contact

ROBERTS GORDON

®

at

Tel: +44(0) 121 506 7709

www.rg-inc.com