Ibed – Roberts Gorden COMBAT CTU 22 TO 115 User Manual

Page 31

Advertising
background image

SECTION 11: C

OMMISSIONING

25

Figure 10: Automatic Burner Control Box Sequence

Burner sequence for Honeywell S4563 or S4565C

Flame Signal

Start Gas Valve

Ignition Spark

Supply 230 V

CLOSE

DOWN

RUN

START

ts**

Signals Output By Control

Flue Fan

Pressure Switch P

C

NO

NC

30 Sec. Purge*

*Purge time begins at pressure switch change over.

**ts=Safety time (S4563C=3 seconds [alternate 5 seconds]; S4565C=5 seconds)

Required Incoming Signals

If at any stage the flame fails, the control will go to "lockout". The red light will illuminate and the
control will need to be manually reset before any further start attempt can be made.

Figure 11: Gas Valve for Heater (Models 22 - 60)

Regulator

(Under Cover)

Inlet Pressure

Gas Inlet

Ignition Control

(Plugs into Gas Valve)

12 Cable Connector

Outlet Pressure

Fixing Screw

Ignition

Output

Flame

Probe

Connection

End View