Section 3: critical considerations – Roberts Gorden COMBAT CTU 22 TO 115 User Manual

Page 9

Advertising
background image

SECTION 3: C

RITICAL

C

ONSIDERATIONS

3

SECTION 3: CRITICAL CONSIDERATIONS

3.1 Basic Information

CTU heaters have automatic ignition burners for
ON/OFF operation only.

3.2 Location and Suspension

All models:

• Must be installed indoors.

• Must be installed in a level position.

• May be mounted on a shelf of non-combustible

material. (

See Page 5, Section 4 and Page 9,

Figure 2 for support points)

• May be suspended from above (

See Page 9,

Figure 2) or from wall brackets of sufficient
strength to support the heater as listed in the
Dimension Data Table

on Page 5, Section 4.1.

Drop rods must be a minimum of 10 mm diame-
ter mild steel. Four suspension points (M10 nuts)
are located on top of the heater.

• Must be installed in a manner which allows the

hinged door to be fully opened to provide access
to all serviceable components.

3.3 Minimum Required Installation Clearances

Clearances around the heater and flue must be as
indicated

on Page 4, Figure 1, Page 10, Figure 3

through Page 11, Figure 6 to ensure access for
servicing, and correct operation.

3.4 Clearances to Combustibles

Clearances must be as indicated

on Page 4, Figure

1. If clearances to combustibles are not indicated,
then installation clearances apply.

3.5 Ventilation

It is important to ensure that there is adequate air
circulation around the heater to supply air for
combustion, ventilation and distribution in
accordance with local and national codes.

3.6 Gas Supply

It is important that the gas supply pipe is sized
correctly to provide the inlet pressure as stated on
the heater data plate. The gas supply pipe and
electrical connections must not support any of the
heater's weight.

3.7 Electrical Supply

A permanent 230 V 50 Hz electrical supply is
required at the main electrical terminals. The heater
also requires suitable energy controls in accordance
with

Section 10.

3.8 Flue

Choose heater siting to allow for the proper location
of the flue. Each heater must be fitted with an
individual and correctly sized sealed flue system
(

See Page 10, Section 6).

No other appliance may be connected to the flue.

For room sealed installation, the air intake must be
the same size sealed system and the flue/air intake
must terminate at an approved concentric wall or
roof terminal.

Advertising