SECTION 14: CONVERSION BETWEEN GASES

14.1 General

Conversion between gasses will require a change of
burner injectors and the gas valve re-commissioning
to the new conditions.

14.2 Burner Conversion

Conversion of the burner assembly from one gas to
the other is the same for all types of heaters.

1. Remove the burner compartment cover as

shown

on Page 36, Section 16.2.

2. Remove the connection between the gas valve

outlet and the manifold.

See Page 35, Section

16.1 for gas valve removal.

3. Remove the manifold from the burner assembly

by removing the screws at the top and bottom.
See Page 36, Section 16.2.1.

4. Remove the main burner injectors.

5. Replace with the injectors for the new gas

ensuring a gas tight seal.

6. Refit all components in reverse order.

14.3 Gas Valves

All gas valves used on the CTU have pressure
regulators that may be set to operate on natural gas
or LPG.

Conversion is carried out by re-setting the burner
pressure to the value in the data table during
commissioning.

See Page 8, Section 4.4.

Ensure that the gas inlet pressure to the heater is
correct for the new gas, and that the gas supply has
been purged of the old gas.