16.2 Burner Compartment

Remove flexible

air duct from spigot

Remove

access plate

Remove screws and

pull off burner cover

Viewing port

for flame probe

Viewing port

for ignition electrode

Flame probe

Burner

compartment

cover

Rubber Seal

Ignition electrode

The burner compartment is a sealed
compartment. Following any work,

re-seal the compartment with the gas
pipe rubber seal fully in place and all
screws fitted and tight.

16.2.1

Remove manifold

screws and pull

out manifold

Manifold

Burners

Injectors

Burner

Screws

Burner

venturi

Unscrew

Injectors

Manifold

Marking

Ensure gas tight fitting of injectors.

Ensure correct alignment with burners.

Ensure all pipe joints are gas tight.

Burner Injectors

MODEL

CTU-22

CTU-30

CTU-35

CTU-40

CTU-50

CTU-60

CTU-75

CTU-90

CTU-100

CTU-115

Injector Quantity

5

5

6

7

9

11

12

14

15

17

Natural Gas (G20) and (G25)

Injector size mm Ø

2.08

2.25

2.25

2.25

2.25

2.25

2.71

2.71

2.71

2.71

in Ø

0.0819

0.0886

0.0886

0.0886

0.0886

0.0886

0.1067

0.1067

0.1067

0.1067

Marking

45

225

225

225

225

225

36

36

36

36

RG P/N

91930045 91930225 91930225 91930225 91930225 91930225 91930036 91930036

91930036 91930036

LPG Gas Propane (G31) and LPG Gas Butane (G30)

Injector size mm Ø

1.25

1.40

1.40

1.40

1.40

1.35

1.51

1.51

1.51

1.51

in Ø

0.0492

0.0551

0.0551

0.0551

0.0551

0.0531

0.0594

0.0594

0.0594

0.0594

Marking

125

54

54

54

54

135

53

53

53

53

RG P/N

91930125 91930054 91930054 91930054 91930054 91930135 91930053 91930053

91930053 91930053

Advertising