Section 4: critcal considerations, Warning, Danger – Roberts Gorden Compact Tubular Unit Heaters CTCU 27 User Manual

Page 13

Advertising
background image

SECTION 4: C

RITCAL

C

ONSIDERATIONS

7 of 42

SECTION 4: CRITCAL CONSIDERATIONS

4.1 Ventilation

It is important to ensure that there is adequate air
circulation around the heater to supply air for
combustion, ventilation and distribution in
accordance with local and national codes.

4.2 Gas Supply

It is important that the gas supply pipe is sized
correctly to provide the inlet pressure as stated on
the heater data plate. The gas supply pipe and
electrical connections must not support any of the
heater's weight.

4.3 Electrical Supply

A permanent 230 V 50 Hz 1Ø electrical supply is
required at the main electrical terminals. The heater
also requires suitable energy controls in accordance
with

Section 10.

4.4 Flue

Choose heater siting to allow for the proper location
of the flue. Each heater must be fitted with an
individual and correctly sized sealed flue system
(

See Page 13, Section 7).

No other appliance may be connected to the flue.

For room sealed installation, the air intake must be
the same size sealed system and the flue/air intake
must terminate at an approved concentric wall or
roof terminal.

WARNING

Carbon Monoxide Hazard

Heaters may be installed vented or unvented.

Vented heaters must be vented outdoors.

Unvented heaters must be installed in
buildings with ventilation rates as per
section 7.

Failure to follow these instructions can result
in death or injury.

DANGER

Electrical Shock Hazard

Disconnect electric before service.

Heater must be properly grounded.

Failure to follow these instructions can result
in death or electrical shock.

Advertising