16.6 Pressure Switch

Pull off 3 way connector. Spring open plastic clips of
mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches
are colour coded for each pressure setting.

Carry out a commission after working on or
changing a pressure switch.

See Page 21, Section

11.

Carbon Monoxide Hazard

Use correct pressure switch specified for each
model.

Use of incorrect pressure switch could cause
unsafe condidtion.

Failure to follow these instructions can result
in death or serious injury.

WARNING

Pressure Switch

CTCU-7

CTCU-11

CTCU-15

CTCU-22

CTCU-27

CTCU-32

RG P/N

90439812

90439812

90439812

90439803

90439810

90439810

Colour Code

orange

orange

orange

grey

black

black

Set Point mbar

0.45

0.45

0.45

1.02

0.82

0.82

in wc

0.18

0.18

0.18

0.41

0.35

0.35

Advertising