Figure 12: gas valve for heater (models 7 - 32) – Roberts Gorden Compact Tubular Unit Heaters CTCU 27 User Manual

Page 29

Advertising
background image

SECTION 11: C

OMMISSIONING

23 of 42

Figure 12: Gas Valve for Heater (Models 7 - 32)

11.4.2 Commissioning the Gas Valves (all gases)

11.4.2.1 Check Burner Gas Pressure

1. Loosen the screw cover of the outlet (burner)

pressure test point and connect a manometer.

2. With the burner firing, measure the pressure on

the manometer. To adjust the burner pressure,
remove the regulator cover from the valve and
turn the regulator adjustment screw to set the
required burner pressure as stated in the Tech-
nical Data Tables for the correct gas and model
on Page 9, Section 5.3.

NOTE: If the correct burner pressure cannot be
reached, then check the inlet pressure to the valve,
with the burner firing. See Technical Data Tables

on

Page 9, Section 5.3 for inlet pressure requirement.
Do not continue to adjust the regulator if the
pressure is not changing.

If the inlet pressure is too low to allow correct burner
pressure setting, then the gas inlet pressure must be
corrected before completing the commission.

Check Gas Rate

1. After burner pressure adjustment, allow the

heater to operate for at least 15 minutes and
then re-check settings.

2. Remove the manometer and refit all covers to

the valve and tighten the screw of the outlet
pressure tap.

3. Check gas flow rate at gas meter.

11.5 Combustion Testing

The only adjustment to alter combustion
performance is burner pressure. Combustion quality

must be tested to prove correct heater operation.
Incorrect results will indicate faults with the
installation or appliance.

Combustion testing must be carried out with all
covers in place. The flue gas is sampled in the flue,
within 1 meter of the heater. The values of CO

2

should be between 5.7% to 8.0% for natural gas and
6.8% to 9.2% for LPG dependant upon model.

The CO will be up to 80 ppm (0.008%) dry, air free
dependant upon model. Temperature rise of the flue
gases above ambient should be approximately

130° C to 160° C. Seal test hole in flue after testing.

Pressure Switch:The pressure switch is factory pre-
set for each model and is not adjustable.

11.6 Turning Off the Heater

Set the external controls to the off position and the
main burner will stop.

The fans will run until they are stopped automatically
by the fan thermostat.

Do not use electrical isolator for control of
heater. Electrical isolator will switch off the fan.
Heat exchanger could be damaged. Warranty will
not cover damage to the heat exchanger if
operated improperly.

11.7 External Controls

External controls may include time switch, room
thermostat and frost thermostat. Operate each
control to ensure that they function correctly. Set the
time switch (if fitted) and room thermostat to the
users’ requirements.

Advertising