Omron W343-E1-07 User Manual

Page 111

Advertising
background image

90

Sending Commands From a PC

Section 5-3

Communications Flags

The execution status of the SEND(090), RECV(098), and CMND(490) instruc-
tions is always reflected by the communications flags (i.e., the Communica-
tions Port Enabled Flag and the Communications Port Error Flag). The CS/
CJ-series CPU Unit’s communications flags are allocated in the Auxiliary Area
as shown in the following table.

Note With CS/CJ-series PCs, communications ports 0 to 7 are also used for exe-

cuting the PCMR(260) (PROTOCOL MACRO) instruction, so these flags are
used in common for SEND(090), RECV(098), CMND(490), and PCMR(260).
While PCMR(260) is being executed, SEND(090), RECV(098), and
CMND(490) cannot be executed at the same communications port.

Communications Port
Completion Codes

The status of a SEND(090), RECV(098), and CMND(490) instruction after
execution is reflected as a communications port completion code, in one word
(two bytes) of data as shown in the following table. (The value is 0000 during
instruction execution.) The recorded status is saved until execution of the next
instruction.

The meanings of the communications port completion codes are the same as
those for FINS commands and responses. When CMND(490) is used, how-
ever, even if a FINS command has an abnormal completion, it will not be
reflected in the communications port completion code. For details, refer to
Communications Port Error Flag and Completion Codes for CMND(490)
below.

Bits 08 to 15 in the communications port completion code correspond to the
first byte of the response code, and bits 00 to 07 correspond to the second
byte. For details, refer to 10-6 Troubleshooting with Response Codes.

Flag name

Address

Contents

Word

Bits

Communications Port
Enabled Flag

A202

Bit 7: Port 7
Bit 6: Port 6
Bit 5: Port 5
Bit 4: Port 4
Bit 3: Port 3
Bit 2: Port 2
Bit 1: Port 1
Bit 0: Port 0

OFF: Execution enabled
(being executed)

ON: Execution disabled
(not being executed)

Communications Port
Error Flag

A219

Bit 7: Port 7
Bit 6: Port 6
Bit 5: Port 5
Bit 4: Port 4
Bit 3: Port 3
Bit 2: Port 2
Bit 1: Port 1
Bit 0: Port 0

OFF: Normal completion
ON: Abnormal completion

Word

Contents

A203

Communications Port 0 Completion Code

A204

Communications Port 1 Completion Code

A205

Communications Port 2 Completion Code

A206

Communications Port 3 Completion Code

A207

Communications Port 4 Completion Code

A208

Communications Port 5 Completion Code

A209

Communications Port 6 Completion Code

A210

Communications Port 7 Completion Code

Advertising