Command/Response Reference

Section 11-3

11-3-20 IP ADDRESS WRITE

Write the local IP address and the subnet mask in the CPU Bus Unit System
Setup.

This command is supported for CJ-series Ethernet Units only.

Command Block

Response Block

Parameters

IP Address (Command)

Specify the local IP address of the Ethernet Unit using 4 pairs of hexadecimal
numbers in the range 00.00.00.00 to FF.FF.FF.FF (0.0.0.0. to
255.255.255.255 decimal). If 0.0.0.0 is specified, the local IP address set in
the allocated words in the DM Area is enabled.

Example: 150.31.2.83

Subnet Mask (Command)

Specify the local IP address of the Ethernet Unit using 4 pairs of hexadecimal
numbers in the range 00.00.00.00 to FF.FF.FF.FF (0.0.0.0. to
255.255.255.255 decimal).

Example: 255.255.255.255

Response Codes

Precautions

The local IP address and subnet mask set using this mask are written to the
CPU Bus Unit System Setup for the Ethernet Unit. For details, refer to

4-2

CPU Bus Unit System Setup.

The new local IP address and subnet mask settings will not be effective until
the PC is restarted or the Ethernet Unit is reset.

57

27

Command
code

Subnet mask

IP address

57

27

Command
code

Response
code

1F

96

53

02

FF

FF

00

FF

Response code

Description

0000

Normal

1001

Command too large

1002

Command too small