Controller data read, 3-2 controller data read, Command block response block parameters – Omron W343-E1-07 User Manual

Page 239: Response codes

Advertising
background image

218

Command/Response Reference

Section 11-3

11-3-2 CONTROLLER DATA READ

Reads the following data from the Ethernet model, version, IP address, sub-
net mask, FINS UDP port number, mode settings, Ethernet address.

Command Block

Response Block

Parameters

Model, Version
(Response)

The Ethernet Unit mode and version are returned as ASCII characters occu-
pying 20 bytes each (i.e., 20 characters each). If all bytes are not used, the
remaining bytes will be all spaces (ASCII 20 Hex).

Example Model:

CS1W-ETN01, CS1W-ETN11, CJ1W-ETN11

Version:

V1.00

IP Address, Subnet Mask
(Response)

The Ethernet Unit’s IP address and subnet mask are returned as 4 bytes
each.

FINS UDP Port Number
(Response)

The Ethernet Unit’s UDP port number for FINS is returned as 2 bytes.

Mode Setting (Response)

The mode setting in the system setup is returned.

Broadcast Setting

0:

All 1s for host number (4.3BSD specification)

1:

All 0s for host number (4.2BSD specification)

IP Address Conversion

00, 01: Automatic generation
10:

IP address table

11:

Both methods (IP address table + automatic generation)

FINS UDP Port Number Designation

0:

Default value (9600)

1:

System setup value

Ethernet Address
(Response)

The Ethernet address of the Ethernet Unit is returned. The Ethernet address
is the address marked on the label on the side of the Ethernet Unit.

Response Codes

01

05

Command
code

01

05

Command
code

Response
code

20 bytes

20 bytes

4 bytes

4 bytes

6 bytes

Model

Version

IP address

Subnet
mask

FINS UDP
port number

Mode
setting

Ethernet
address

Others all 0

Broadcast setting

IP address conversion

FINS UDP port number
designation

00

Bit 15

Response code

Description

0000

Normal

1001

Command too large