Command/Response Reference

Section 11-3

Command Block

Response Block

Results Storage
Format

Parameters

UDP Socket Number
(Command)

The UDP socket number to send the data specified as 2 bytes between 1 and
8.

Results Storage Area
(Command)

The area in which the result of the command execution is stored. The first byte
specifies the memory area and data type (variable type). The 2nd to 4th bytes
specify the beginning address of the results storage area. Refer to page 216
for details about the variable types and addresses that can be specified.

Destination IP Address
(Command)

The IP address of the node to which data is being sent.

Destination UDP Port
Number (Command)

The UDP port number of the node to which data is being sent.

Number of Bytes Sent
(Command, Results
Storage Area)

The number of bytes in the data sent by this command. Up to 1,984 bytes can
be specified, or up to 1,472 bytes can be specified if the broadcast address is
specified as the send destination. The results storage area stores the actual
number of bytes sent.

Send Data (Command)

Specifies the data sent to the remote node.

Response Codes

03

27

Command
code

UDP
socket
number

Results storage area

Destination IP
address

Destination
UDP port
number

Number of
bytes sent

1984 bytes max.

Send data

03

27

Command
code

Response
code

Response
code

Number of
bytes sent

Response code

Description

0000

Normal

0105

Local IP address setting error

0302

CPU Unit error; execution not possible.

1001

Command too large

1002

Command too small

1003

The number of bytes sent does not match the sent data
length.

1100

UDP socket number or number of bytes sent is out of range.
The destination IP address is 0.
Local UDP port number is 0.

1101

The variable type for the results storage area is out of range.

1103

Non-zero bit address specified for the results storage area.

220F

Specified socket is currently sending.

2210

The specified socket is not open.

2211

High traffic at Unit; cannot execute service.