xx

Application Precautions

5

• Mounting or dismounting I/O Units, CPU Units, Inner Boards, or any

other Units.

• Assembling the Units.

• Setting DIP switches or rotary switches.

• Connecting cables or wiring the system.

!Caution Failure to abide by the following precautions could lead to faulty operation of

the PC or the system, or could damage the PC or PC Units. Always heed
these precautions.

• Fail-safe measures must be taken by the customer to ensure safety in the

event of incorrect, missing, or abnormal signals caused by broken signal
lines, momentary power interruptions, or other causes.

• Interlock circuits, limit circuits, and similar safety measures in external cir-

cuits (i.e., not in the Programmable Controller) must be provided by the
customer.

• Always use the power supply voltages specified in the operation manuals.

An incorrect voltage may result in malfunction or burning.

• Take appropriate measures to ensure that the specified power with the

rated voltage and frequency is supplied. Be particularly careful in places
where the power supply is unstable. An incorrect power supply may result
in malfunction.

• Install external breakers and take other safety measures against short-cir-

cuiting in external wiring. Insufficient safety measures against short-cir-
cuiting may result in burning.

• Be sure that all the mounting screws, terminal screws, and cable connec-

tor screws are tightened to the torque specified in the relevant manuals.
Incorrect tightening torque may result in malfunction.

• Leave the label attached to the Unit when wiring. Removing the label may

result in malfunction if foreign matter enters the Unit.

• Remove the label after the completion of wiring to ensure proper heat dis-

sipation. Leaving the label attached may result in malfunction.

• Use crimp terminals for wiring. Do not connect bare stranded wires

directly to terminals. Connection of bare stranded wires may result in
burning.

• Wire all connections correctly.
• Double-check all wiring and switch settings before turning ON the power

supply. Incorrect wiring may result in burning.

• Mount Units only after checking terminal blocks and connectors com-

pletely.

• Be sure that the terminal blocks, Memory Units, expansion cables, and

other items with locking devices are properly locked into place. Improper
locking may result in malfunction.

• Check the user program for proper execution before actually running it on

the Unit. Not checking the program may result in an unexpected opera-
tion.

• Do not lay communications cables near power lines or high-voltage lines.
• Always lay communications cables in ducts.