17. If communications are adversely affected by noise from the Unit’s power

supply terminals, the problem may be solved by implementing the mea-
sures shown below.

a) Add to the communications retry processing at the application. In par-

ticular, noise resistance capacity can be improved by increasing the
number of retries for applications using UDP.

b) Insert a noise filter right next to the Unit’s power supply terminals.

Power Supply
Specifications

The following table shows the power supply specifications. Make sure that
these specifications are met.

OMRON’s S82J Series is recommended for the power supply.

General Switching Power Supply Configuration

Communications Power Supply Isolation Method

AC power supply

AC input

DC output

Case

S8J2 Power Supply

S82Y-

@@N (Mounting Stand)

DC power supply

Insulating material (bakeboard, acrylic board, etc.)

(1) When S82J is used.

(2) When another power supply is used.

Switching power supply

Power
supply
circuit

Standard Switching Power Supply Circuit

24 VDC

Noise filter

24-VDC power supply

As close as possible

Recommended filter: MAS-1206-33 by Nemic-Rambda K.K.

Specifications

Rated voltage: 250 V (AC, DC)

Rated current: 6 A

Dimensions

105.5 x 52.5 x 40 mm (W x H x D)
(Not including connector.)

Item

Specifications

Power supply voltage

24 VDC

Allowable power supply voltage
fluctuation

20.4 VDC to 26.4 VDC (24 VDC –15% + 10 %)

Current consumption

300 mA max. at 24 VDC (per node)

Inrush current

2.5 A max. (24 VDC when rise time is 5 ms)