137

Using Socket Services with Socket Service Request Switches

Section 6-2

UDP Receive
When the UDP Receive Bit (CIO 000003) turns ON, the
UDP Receive Error Flag (CIO 000103) is turned OFF and
the UDP Receiving Flag (CIO 000203) is turned ON to
initialize processing.

If the Send Request Switch (CIO 151903) turns OFF while
the UDP Sending Flag (CIO 000200) is OFF, the contents
of the response code (D30027) in the Socket Service Pa-
rameter Area is checked, and if it is not 0000 Hex (normal
end), the UDP Send Error Flag (CIO 000102) is turned ON.

After the execution results have been checked, the UDP
Send Bit (CIO 000002) is turned OFF.

After the parameters have been set, the Send Request
Switch (CIO 151903) is turned ON and the UDP Sending
Flag (CIO 000202) is turned OFF.

Continued from previous page.

MOV(21)

000002

000202

MOV(21)

MOV(21)

MOV(21)

SET

000002

RSET

000202

@RSET

000003

@SET

SET

000002

000202

151903

<>(305)

RSET

000002 000202

151903

Continued on next page.

MOV(21)

MOV(21)

MOV(21)

When the UDP Sending Flag (CIO 000202) turns ON, the
following parameters are written to the parameter area for
socket number 1.
D30018: 0001 Hex = UDP/TCP socket No. 1
D30020 and D30021:

C424 2037 Hex =
Remote IP address 196.36.32.55

D30022: 1000 Hex = Remote UDP/TCP port No. 4096
D30023: 0064 Hex = No. of send/receive bytes is 100
D30024 and D30025:

8200 0000 Hex =
Send/receive data address D00000

#0001

D30018

#C424

D30020

#2037

D30021

#1000

D30022

#0064

D30023

#8200

D30024

#0000

D30025

151903

000202

000102

000002

000103

000203

D30027

#0000

Advertising